SEALING FITTINGS FOR HAZARDOUS LOCATIONS.

COPPER FREE ALUMINUM

EYS SERIES

    • For dimensions:
      See Spec Sheet R007-RW-321

      Class I, Div. 1 & 2, group A, B, C, D.
      Class II, Div. 1 & 2, group E, F, G.
      Class lll, Div. 1 & 2.

    • • Explosionproof
    • • Dust-ignitionproof
    • • Raintight
    • • Wet locations

APPLICATIONS:

    • Restrict the passage of gases, vapors, liquids, dust and flames from one portion of the electrical installation to another at atmospheric pressure and normal ambient temperatures.
    • Saline chamber test to paint according to ASTM B117.
    • Paint adhesion test according to ASTM 3359.
    • Resistence to mechanicals impacts to body according to IK09, thanks to its design that does not have elements susceptible to breakage.
    • NPT threaded for use with RIGID conduit.
    • Vertical and Horizontal positions.
    • 25% fill conduit

MATERIAL:

    • Diecast copper free aluminum

FINISH:

    • Electrostatic powder epoxy/polyester polymerized coating. Minimum thickness 2 mils.

OPTIONAL:

    • Galvanized steel removable Nipple

INSTRUCTIONS:

  • Are to be installed within 18″ of a device that produce sparks, arcs or high temperature.
  • The thickness of the sealing compound shall not be less than the trade size of conduit and in no case less than 5/8″.
  • Manufactured in compliance with:
  • UL 886, UL 1203.
  • CAN/CSA-C22.2 No. 30
Scroll to Top